PRODUCT > Halogen Free

본문 바로가기
PRODUCT

Halogen Free

450/750V halogen free flame retardant polyolefin insulation wire (HFIX)

Usage

  • Used for indoor distrubution line under 450/750V grade and less the maximum permissible conductor temperature of 90℃ insulated Halogen free crosslinked polyolefin

Applied specification

  • KS C 3341, Elctrical appliance safety standard

Structure

  • Conductor : Solid (Class 1) or Standed Annealed Copper (Class 2)
  • Insulation : Halogen free flame retardant Closslinked Polyolefin
  • Color of the insulation : black, white, red, green, yellow, blue
  • Maximum allowable temperature : 90℃

Conductor Insulation
Thickness
(Standard)
Standard
Overall Diameter
Max.
Conductor
Resistance
at 20℃
Test Voltage Approx.
Weight
Copper
Nominal
Sectional
Area
Class Min. Max.
Ω/㎞ kV ㎏/㎞
1.5 1 0.7 2.6 3.3 12.1 2.5 20
2.5 1 0.8 3.2 4.0 7.41 2.5 40
4 1 0.8 3.6 4.6 4.61 2.5 50
6 1 0.8 4.1 5.2 3.08 2.5 70
10 1 1.0 5.3 6.6 1.83 2.5 120
1.5 2 0.7 2.7 3.4 12.1 2.5 20
2.5 2 0.8 3.3 4.1 7.41 2.5 40
4 2 0.8 3.8 4.7 4.61 2.5 50
6 2 0.8 4.3 5.4 3.08 2.5 70
10 2 1.0 5.6 7.0 1.83 2.5 120
16 2 1.0 6.4 8.0 1.15 2.5 170
25 2 1.2 8.1 10.1 0.727 2.5 260
35 2 1.2 9.0 11.3 0.524 2.5 350
50 2 1.4 10.6 13.2 0.387 2.5 480
70 2 1.4 12.1 15.1 0.268 2.5 670
95 2 1.6 14.1 17.6 0.193 2.5 920
120 2 1.6 15.6 19.4 0.153 2.5 1,160
150 2 1.8 17.3 21.6 0.124 2.5 1,430
185 2 2.0 19.3 24.1 0.0991 2.5 1,780
240 2 2.2 22.0 27.5 0.0754 2.5 2,320
300 2 2.4 24.5 30.6 0.0601 2.5 2,930